Energies · 2016 · 44 citations · 17 references
EngineeringElectrical EngineeringHeat TransferThermal AnalysisTransport PhenomenaElectrical System DiagnosticsInsulation SystemsMoisture TransportRelative HumidityCondition Monitoring Of InsulationMoisture ContentMoisture Content EffectsMoisture Effects In InsulationMoisture MigrationPartial DischargeTransformer Insulation
Most power transformers operating in a power system possess oil-paper insulation. A serious defect of this type of insulation, which is associated with long operation time, is an increase in the moisture content. Moisture introduces a number of threats to proper operation of the transformer, e.g., ignition of partial discharges (PDs). Due to the varying temperature of the insulation system during the unit’s normal operation, a dynamic change (migration of water) takes place, precipitating the oil-paper system from a state of hydrodynamic equilibrium. This causes the PDs to be variable in time, and they may intensify or extinguish. Studies on model objects have been conducted to determine the conditions (temperature, humidity, time) that will have an impact on the ignition and intensity of the observed phenomenon of PDs. The conclusions of this study will have a practical application in the evaluation of measurements conducted in the field, especially in relation to the registration of an online PD monitoring system.
17
Moisture equilibrium in transformer paper-oil systems
Yanqing Du, Markus Zahn, Bernard C. Lesieutre et al. · IEEE Electrical Insulation Magazine · 1999 · 371 citations · Full text
Chandima Ekanayake, Stanislaw Gubanski, A. Graczkowski et al. · IEEE Transactions on Power Delivery · 2006 · 261 citations
Natural Sciences, Electrical Engineering, Materials Science +17
Diagnostic Measurements for Power Transformers
Stefan Tenbohlen, Sebastian Coenen, Mohammad Djamali et al. · Energies · 2016 · 185 citations · Full text
Engineering, Electrical Engineering, Condition Assessment +10