Plasma Science and Technology · 2016 · 31 citations · 7 references
EngineeringElectrical EngineeringPhysicsElectromagneticsPlasma PhysicsPropagationInsulation SystemsLightning PropagationExperimental Study DesignHigh Humidity StressHigh-speed ImagingHigh-voltage InsulationHigh-voltage SystemsHumidityStreamer DischargesStreamer Formation
One of the main problems in the Ultra High Voltage (UHV) transmission project is to choose the external insulation distance, which requires a deep understanding of the long air gap discharge mechanism. The leader-streamer propagation is one of most important stages in long air gap discharge. In the conductor-tower lattice configuration, we have measured the voltage, the current on the high voltage side and the electric field in the gap. While the streamer in the leader-streamer system presented a conical or hyperboloid diffuse shape, the clear branch structure streamer in front of the leader was firstly observed by a high speed camera in the experiment. Besides, it is found that the leader velocity, width and injected charge for the branch type streamer are greater than those of a diffuse type. We propose that the phenomenon results from the high humidity, which was 15.5-16.5 g/m3 in our experiment.
7
A self-consistent upward leader propagation model
Marley Becerra, Vernon Cooray · Journal of Physics D Applied Physics · 2006 · 181 citations · Full text
Electric field step in air gap streamer discharges
Rong Zeng, Chijie Zhuang, Zhanqing Yu et al. · Applied Physics Letters · 2011 · 44 citations