Measurements of the voltage induced on an overhead power line 20 m from triggered lightning

Marcos Rubinstein, M. A. Uman, Pedro J. Medelius, E. M. Thomson

IEEE Transactions on Electromagnetic Compatibility · 1994 · 56 citations · 8 references

Concepts

Abstract

Voltages induced on a 448-m power distribution line by eleven return strokes in three lightning flashes artificially initiated 20 m from one end of the distribution line and the corresponding vertical electric fields at 500 m have been measured. Two types of induced-voltage waveforms were recorded: oscillatory and impulsive. The former exhibit peak values that range from tens of kilovolts to about 100 kV; the latter show peak voltages nearly an order of magnitude larger. Both types of induced voltage waveforms were observed to occur for different strokes within a single flash. Relatively successful modeling of the oscillatory voltage waveforms is presented. Modeling of the impulsive waveforms proved unsuccessful, probably due to those waveforms being in part associated with a failure, perhaps an unexpected flashover, in the measuring system.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

References

8