EngineeringElectrical EngineeringAir PollutionAtmospheric ElectricityCircuit TheoryCurrent DistributionCurrent-voltage CharacteristicsElectrical Hazard AssessmentElectrical Hazard IdentificationCurrent Distribution AnalysisFlashoverFlashover ModelingHarmonic ResponseLeakage CurrentLeakage Current AnalysisLeakage Current Detection
In order to establish a method for monitoring contamination in insulators based on leakage current waveforms and their frequency characteristics, the leakage current waveforms and frequency characteristics of an artificially polluted 180 mm diameter cap and pin type insulator were investigated by the wet contaminant and the clean fog methods at fixed applied voltages. As a result it was found that leakage current waveforms become similar to the symmetrical wave when strong local arcs occur; hence, the intensity of the odd order of harmonic components, e.g. 50, 150, and 250 Hz, is high. Furthermore, it was clarified that the transition of the leakage current waveforms, until flashover occurs, is classified into six stages and that a threshold exists by which the occurrence of flashover can be predicted.