IEEE Transactions on Dielectrics and Electrical Insulation · 1997 · 17 citations · 9 references
EngineeringElectrical EngineeringPhysicsElectronic MaterialsHeat TransferMicroelectronicsCurrent-voltage CharacteristicsElectric PotentialAvalanche BreakdownBreakdown MechanismsDirect Current DischargesVoltageVoltage Interruption
The aim of this project was to find a correlation between contact gap length and switching behavior of a vacuum circuit breaker. A large number of interruption experiments were executed in a vacuum chamber with butt type contacts made of Cu, CuCr 50/50 and AgWC. The currents to be interrupted varied from 2.5 to 32 kA. The rate of change of current and recovery voltage were kept at a fixed value at current zero. Many re-ignitions of the dielectric type, scattered over a wide range of re-ignition voltages, were observed and only a few of the thermal type. The total amount of energy dissipated in the vacuum chamber appears to be determinative for the type of re-ignition. On Cu severe anode spot melting was found, whereas CuCr and AgWC suffered little anode melting. The wide range of re-ignition voltage values found shows that a straight correlation with the contact gap length can not be defined. At 5 to 10 /spl mu/s after current zero a 'second' post arc current did appear.
9
H. Craig Miller · IEEE Transactions on Plasma Science · 1983 · 86 citations
Post Arc Current of Vacuum Interrupters
S. Yanabu, M. Homma, E. Kaneko et al. · IEEE Transactions on Power Apparatus and Systems · 1985 · 72 citations