Repetitive-Based Controller for a UPS Inverter to Compensate Unbalance and Harmonic Distortion

G. Escobar, J. Leyva-Ramos, Paolo Mattavelli

IEEE Transactions on Industrial Electronics · 2007 · 294 citations · 21 references

Concepts

TL;DR

The paper introduces a repetitive‑based controller for a UPS inverter. The controller is realized as a simple feedback array with a delay line, employing negative feedback and feedforward paths to target odd harmonics. Experimental results confirm that the controller, equivalent to a bank of resonant filters, effectively rejects harmonic distortion from unbalanced loads, enabling the UPS inverter to produce an almost pure sinusoidal balanced voltage.

Abstract

This paper discusses a repetitive-based controller for an uninterruptible power supply (UPS) inverter. It is shown that a bank of resonant filters, used as a refinement term for harmonic compensation in earlier works, is equivalent to a repetitive scheme with a particular structure. The latter is implemented using a simple feedback array with a delay line, thus making the implementation relatively easy. More precisely, the repetitive scheme takes a negative feedback structure plus a feedforward path whenever the odd harmonics are considered for compensation only. The repetitive scheme, equivalent to the bank of resonant filters, acts as a refinement term to reject the harmonic distortion caused by the unbalanced and distorted load current, and thus, allowing the UPS inverter to deliver an almost pure sinusoidal balanced voltage. Experimental results in a 1.5 KVA three-phase inverter are included to show the performance of the proposed controller

References

21