Implementation of Fault Ride-Through Techniques of Grid-Connected Inverter for Distributed Energy Resources With Adaptive Low-Pass Notch PLL

Dongsul Shin, Kyoung-Jun Lee, Jong-Pil Lee, Dong-Wook Yoo, Hee‐Je Kim

IEEE Transactions on Power Electronics · 2014 · 105 citations · 50 references

Concepts

TL;DR

Distributed energy resources are rapidly expanding, and their high power ratings necessitate grid codes that require robust phase‑locked loops to accurately extract grid phase under harmonic and unbalanced conditions. The study proposes fault‑ride‑through techniques using a low‑pass notch PLL and a universal six‑parameter voltage sag generator to validate low‑voltage ride‑through performance across grid codes. The LPN‑PLL delivers fast, smooth transient responses to sudden grid voltage changes and remains robust under distorted and unbalanced conditions, as demonstrated experimentally with a 10 kV·A three‑phase inverter and the sag‑generator prototype. Experimental results indicate that the LPN‑PLL enables stable operation during grid faults without tripping the system.

Abstract

The amount of distributed energy resources (DERs) has constantly increased worldwide. As the power ratings of DERs have become considerably high, the grid code requirements are necessary to secure reliable power generation and transmission for the public electric network. In order to follow grid codes of the various countries and optimize the function of grid-connected inverters for DERs, a robust phase-locked loop (PLL) is essential for extracting the grid phase information accurately, when the grid voltage is polluted by harmonics and unbalanced. This paper proposes fault ride-through techniques based on a low-pass notch (LPN)-PLL. The LPN-PLL has not only fast and smooth transient responses to a sudden transition of the grid voltage but also has robustness to the distorted and unbalanced grid conditions. Therefore, the stable performance in the grid fault conditions is expected without the system trip. Furthermore, a universal voltage sag generator for the various grid codes with six parameters is proposed for the verification of low voltage ride-through (LVRT) performance. Experimental verifications are presented to show the LVRT performance based on the LPN-PLL with a three-phase grid-connected inverter (10 kV·A) and a prototype of the voltage sag generator (10 kV·A).

References

50