2010 · 34 citations · 6 references
EngineeringElectrical EngineeringCircuit TheoryCritical Infrastructure ProtectionPower ElectronicsPower QualityProtection SystemsTransmission LinesFault ProtectionFilter BanksHilbert-huang TransformHvdc TransmissionNatural Boundary ConditionsThreshold ProtectionTransient Signal ProcessingTransmission Line Transients
Smoothing reactors, together with the DC filter banks installed at both ends of the HVDC transmission line constitute the `natural boundary', which leads to significant difference in attenuation characteristic of different frequency components of fault transient signals detected by protection. By means of Hilbert-Huang Transform, which is a kind of non-stationary transient signal processing method, the energy of high frequency components(2000Hz~10kHz) is extracted based on the attenuation characteristic of the line boundary, then a novel algorithm for the non-unit transient-based protection is acquired. Moreover, a protection threshold that is adapt to various lengths of transmission line is obtained by extensive simulation work. Experimental results indicate that the new criteria can identify any internal fault on the whole line and clear it rapidly and credibly, what's more important, the accuracy and reliability of the criteria will not be influenced by the length of the transmission line.
6
Norden E. Huang, Steven Long, Man‐Li C. Wu et al. · Proceedings of the Royal Society A Mathematical Physical and Engineering Sciences · 1998 · 23.3K citations · Full text
Computing, Computational Engineering, Biomedical Signal Processing +16
Study of Non-Unit Transient-Based Protection for HVDC Transmission Lines
Min You, Baohui Zhang, Ruifeng Cao et al. · 2009 · 21 citations