Proceedings of the CSEE · 2007 · 11 citations · 0 references
EngineeringElectrical EngineeringCircuit TheoryCritical Infrastructure ProtectionPower ElectronicsPower QualityProtection SystemsTransmission LinesFault ProtectionTransient Protection DevicesTransmission Line TransientsWavelet TransformWavelet Transform Analysis
On the basis of the characteristics of line boundary, this paper analyzes the different features of internal and external faults. The difference is that the ratio of high frequency to low frequency components in case of one external fault is less than that in case of the same internal fault, in which high frequency is in the band of line trap and low frequency is within 1~10kHz. Based on the different features, the paper presents a new non-unit transient-based protection unit using backward traveling-wave, called boundary unit (BU). The practical BU algorithm is designed using wavelet transform. A number of ATP simulation tests show that the new algorithm is feasible, and ultra-high-speed, and that the BU performance is superior to that of the former non-unit transient-based protection using current traveling-wave. The paper also indicates that the non-unit transient based protection is difficult to reliably protect the whole line, therefore the non-unit transient based protection may be used as an ultra-high-speed unit of the whole-line protection.