Power System Protection and Control · 2010 · 19 citations · 0 references
EngineeringElectrical EngineeringCircuit TheoryCritical Infrastructure ProtectionPower ElectronicsElectric CircuitsEnergy Infrastructure ProtectionLightning ProtectionPower Grid AnalysisPower QualityProtection SystemsFault ProtectionFault Protection SystemsHvdc TransmissionLightning Protection For Power SystemsLightning Protection Of Power LinesProtection CircuitsRelay ProtectionTransient Protection Devices
In order to overcome the shortcomings of current main protection for HVDC lines,a novel protection scheme based on non-unit transient voltage is proposed.Through analyzing the characteristics of smoothing reactors and DC filters located at both ends of the DC line,the working principle and algorithm of the main element——boundary unit,as well as the operation criteria of starting unit,lightning identification unit and fault-pole identificaiton unit are established.Besides,the logic coordination of each element is also presented.Extensive EMTDC simulation experiments show that this protection scheme can accurately and reliably identify DC line faults,with excellent performance of tolerating transition resistances.Also,the relay threshold requires setting only once and needs no more modification as the length of line changes.