<i>Legionella</i> Contamination of a Preoperational Treatment Plant

Lance Voss, Kenneth S. Button, Richard Lorenz, Olli H. Tuovinen

American Water Works Association · 1986 · 10 citations · 16 references

Concepts

Abstract

A study of the distribution of Legionella in a newly constructed water treatment facility found Legionella pneumophila (serogroup 1) in both hot‐ and cold‐water lines. The contamination was monitored by bacterial enumeration of samples collected from various sites in the building and from disassembled plumbing fixtures. Repeated flushing and hyperchlorination were inadequate as decontamination procedures, presumably because the organism had colonized interior spaces of valves and associated parts that are inaccessible to chlorine and unaffected by flushing.