Illinois Digital Environment for Access to Learning and Scholarship (University of Illinois at Urbana-Champaign) · 1994 · 12 citations · 3 references
Open access
EngineeringMechanical EngineeringAir ConditioningEnergy SystemsHeat TransferEnergy StorageEvaporative CoolingRefrigerationRefrigeration CyclesRefrigeration SystemsThermodynamic CyclesCompressor PerformanceCompressor SystemsEfficiencyEfficiency LossEfficient Refrigeration SystemsQuasi-steady-state ApproximationRefrigeration Performance AnalysisSteady-state Behavior
The cycling losses of a domestic refrigerator-freezer are quantified to gain a better understanding of the \nadjustments needed to enable a steady-state refrigerator model to be used to design for cycling operation. A \nrefrigerator with a capillary tube/suction line heat exchanger and a rotary compressor was instrumented extensively \nfor these experiments. Refrigerant migration during the off-cycle was found to increase the cabinet heat load by 2 to \n6%, with the greater percentage increase occurring at lower ambient temperatures. Compared to a quasi-steady \nmachine, the efficiency is degraded by 3 to 5% during the on-cycle due to power and capacity losses. The capacity \nloss, ranging from 3.9 to 5.6%, plays a greater role in the efficiency loss than the power penalty, 0 to 1.5%. During the \nfirst minute of the on-cycle, when the refrigerant is being redistributed from the evaporator to the oil sump, 2 to 3.3% \nof the capacity is lost and the power demand may increase by as much as 1.7%. After the first minute of the on-cycle, \nwhile some refrigerant is being redistributed back into the evaporator, there is a 0.8 to 3.0% capacity loss and a \nnegligible power penalty.