The external insulation of the equipment in the valve hall of ultra high voltage (UHV) dc converter station must be able to withstand ac-dc combined voltage influences. Investigating the surface discharge characteristics of external insulation under ac-dc combined voltage is currently a significant research topic. The investigation into the surface streamer characteristics under ac-dc combined voltage is instrumental in elucidating the mechanism of surface flashover. The streamer characteristics of different phases in a single cycle under ac-dc combined voltage were determined by conducting surface streamer discharge tests. The relationship between surface streamer characteristics and different phases under ac-dc combined voltage was summarized. By comparing the test results of surface streamer discharge under dc voltage, this study analyzed the effect mechanism of ac-dc combined voltage on surface streamer characteristics. The directional motion of space charge under ac-dc combined voltage was identified as the primary determinant of surface streamer characteristics.