IEEE Transactions on Power Systems · 2022 · 39 citations · 22 references
EngineeringElectrical EngineeringDynamical SystemsPower ElectronicsSystem DynamicsControl Of Dynamical SystemsControl SystemsControl TheoryPower System StabilityStabilityStability TheoryLyapunov ControlLyapunov FunctionsLyapunov StabilityPhase-locked LoopsStabilizationSwitched ControlSwitched SystemsSynchronization
Limits of phase locked loop (PLL) are necessary to make sure the transient converter frequency bounded in a safety range. This leads to the grid-connected voltage source converter (VSC) with limits of PLL as one switched system. Stability of switched dynamic system is fully discussed in this paper. One conservative analytical stable region of the unbounded autonomous system is derived by Lyapunov method. It is proved that when bounds are touched, any trajectory of the studied switched system deviates from these bounds at two fixed switching Points. Moreover, the switched system energy is non-increasing when trajectories lie inside the derived analytical stable region. Based on these properties of switched system, it is proved that to ensure the globally asymptotically stability, the fixed switching Points should be placed inside the derived stable region of the unbounded autonomous system. Finally, stabilization method is proposed via placement of the fixed switching Points so that the globally asymptotically stability is ensured.
22
Analysis of D-Q Small-Signal Impedance of Grid-Tied Inverters
Bo Wen, Dushan Boroyevich, Rolando Burgos et al. · IEEE Transactions on Power Electronics · 2015 · 1.3K citations