IEE Proceedings C Generation Transmission and Distribution · 1983 · 68 citations · 0 references
EngineeringElectrical EngineeringAnalog ElectronicsCircuit TheoryFault ToleranceElectrical MeasurementElectrical MetrologyElectrical System DiagnosticsFault DetectionImpedance MatchingNorton Equivalent CircuitsCircuit ImpedanceFault Localization AlgorithmsFault LocationImpedance AnalysisImpedance MeasurementImpedance-based Fault LocalizationReactance TheoryTransmission Line Theory
Fault resistances affect the accuracy of short-circuit location, when distance to the fault is determined by means of measuring reactance at one end of the transmission line. This is because the current which flows through the fault resistance is slightly shifted in phase with respect to the current measured at the end of the line in question, due to the effect of the prefault load current. As a result, the fault resistance is recognised as an apparent impedance with both resistive and reactive components. The latter produces an error in the fault location, as it affects the measured reactance. The paper presents a simple algorithm which compensates for the error, and makes it possible to locate short circuits accurately; even if fault resistances are comparatively high.