Energies · 2021 · 25 citations · 20 references
EngineeringElectrical EngineeringCircuit TheoryPower ElectronicsRenewable Energy SystemsFrequency ResponseFrequency-domain AnalysisPower QualityFrequency Sweep AnalysisVoltage
The paper presents a method for the frequency characterization of voltage transformers (VTs) for medium voltage (MV) grids which involves only sine waves. It is called extended SINDICOMP, since it is an extended version of the previously developed technique SINDICOMP. It requires, in the first step, an evaluation and a compensation of the non-linearity introduced by the VT when it is supplied with a 50 Hz sinusoidal input at rated value. Then, the VT is characterized with a low voltage sinusoidal frequency sweep from the second harmonic frequency up to the first resonance frequency. Some rules to build the approximated frequency response, starting from these two sets of data, are given in the paper. The proposed approach is applied to three commercial MV VTs. Significant improvement of the VT performance is obtained, compared to the use of a frequency response obtained from the low voltage characterization.
20
Frequency Responses of MV voltage transformers in the range of 50 Hz to 10 kHz