IEEE Access · 2020 · 27 citations · 39 references
EngineeringElectrical EngineeringCircuit TheoryMetrologyPower ElectronicsElectrical MetrologyPower Grid AnalysisPower QualityPower SystemsSystem IdentificationTransmission LinesParameter IdentificationPhase AnglePhasor Measurement UnitsPower System ModelingPower System ModellingRobust System IdentificationTransmission Line AnalysisTransmission Line Modeling
Accurate transmission line parameters are the basis of power system calculations. The measured phasor measurement unit (PMU) phase angle data at both ends of a line may contain large errors caused by synchronization problems, which can seriously affect the accuracy of parameter identification. This paper proposes a robust PMU-based method for calculating transmission line parameters from PMU data at both ends of a line in such a way that a synchronization error between the ends does not degrade the results. Specifically, a π-equivalent model for the transmission line is established, and a least square objective function with nonlinear equations for positive parameter identification is derived. Furthermore, to reduce the impact of noise and biased data, median estimation is used to obtain the final result. Finally, a simulation shows the effectiveness and robustness of the proposed method, and its practicality is demonstrated in a case study using measured PMU data.
39
Spoofing GPS Receiver Clock Offset of Phasor Measurement Units
Xichen Jiang, Jiangmeng Zhang, Brian J. Harding et al. · IEEE Transactions on Power Systems · 2013 · 217 citations · Full text