Investigations on the Performance of a New Grounding Device with Spike Rods under High Magnitude Current Conditions

Abdul Wali Abdul Ali, Nurul Nadia Ahmad, Normiza Mohamad Nor, Muhd Shahirad Reffin, Syarifah Amanina Syed Abdullah

Energies · 2019 · 13 citations · 13 references

DOIFull text

Open access

Concepts

Abstract

In many publications, the characteristics of practical earthing systems were investigated under conditions involving fast-impulse currents of different magnitudes by field measurements. However, as generally known, in practice the transient current can normally reach several tens of kiloamperes. This paper therefore aimed to investigate the characteristics of a new electrode for grounding systems under high current magnitude conditions, and compare it with steady-state test results. The earth electrodes were installed in low resistivity test media, so that high impulse current magnitudes can be achieved. The effects of impulse polarity and earth electrode’s geometry of a new earth electrode were also quantified under high impulse conditions, at high currents (up to 16 kA).