Measurements of grounding resistances for high impulse currents

57

Citations

8

References

1998

Year

Abstract

The paper presents field measurements of surge characteristics of a concrete pole, a buried single conductor and a grounding net for high-impulse currents with a maximum magnitude of 40 kA and with the wavefront duration of a few microseconds. The measured results show that the grounding resistances are greatly dependent on the applied currents and have a hysteresis characteristic. Finally, it is made clear that the grounding resistance has an energy dependence.