Distortion of fluorescent lamps in the frequency range 2-150 kHz

Anders Larsson, Martin Lundmark, Math Bollen

Epubl LTU · 2006 · 18 citations · 6 references

Full text

Open access

Concepts

Abstract

This paper presents measurements of voltages and currents taken by fluorescent lamps with high-frequency ballast. The results are discussed in time domain, in frequency domain and in time-frequency domain. A number of different high-frequency components are present: recurrent transients, narrow-band time-invariant signals, and time-dependent signals. The increase in distortion with increasing number of lamps is studied as well. The distortion increases about linear with the number of lamps in the frequency range 2-9 kHz but shows only a minor increase or no increase at all in the frequency range 9-150 kHz.

References

6