2018 · 23 citations · 16 references
EngineeringElectrical EngineeringMicroelectronicsPower ElectronicsSemiconductor DevicesElectronics TechnologyProtection SystemsSemiconductor ReliabilityCircuit Breaker ProtectionCircuit Overload ProtectionDevice Overload ProtectionFault Current ProtectionOverload ProtectionOverload Protection DevicesProtection CircuitsShort-circuit Protection
This paper reports a SiC-based solid-state circuit breaker (SSCB) with an adjustable current-time (I-t) tripping profile for both ultrafast short circuit protection and overload protection. The tripping time ranges from 0.5 microsecond to 10 seconds for a fault current ranging from 0.8X to 10X of the nominal current. The I-t tripping profile, adjustable by choosing different resistance values in the analog control circuit, can help avoid nuisance tripping of the SSCB due to inrush transient current. The maximum thermal capability of the 1200V SiC JFET static switch in the SSCB is investigated to set a practical thermal limit for the I-t tripping profile. Furthermore, a low fault current `blind zone' limitation of the prior SSCB design is discussed and a new circuit solution is proposed to operate the SSCB even under a low fault current condition. Both simulation and experimental results are reported.
16
The Status of DC Micro-Grid Protection
Robert Cuzner, Giri Venkataramanan · 2008 · 258 citations
Engineering, Electrical Engineering, Systems Engineering +17