Standardized survey of transformer reliability: On behalf of CIGRE WG A2.37

Stefan Tenbohlen, Janine Jagers, F. Vahidi

2017 · 57 citations · 0 references

Concepts

Abstract

There is limited literature available in the public domain discussing failure statistics of transformers. This contribution presents the methodology for a standardized failure data acquisition developed by the Cigré Working Group A2.37. The working group collected 964 major failures which occurred in the period 1996 to 2010, within a total population of 167,459 transformer years, contributed by 58 utilities from 21 countries. The overall failure rates of substation transformer were all within 1%. For three groups of substation transformers, detailed population data were collected enabling the calculation of hazard curves. All populations show a low hazard rate and no distinct bathtub curve character. An increasing probability of failure after a particular age, which would justify an exchange of the transformer, cannot be derived from the available data. Windings, tap changer and bushing related failures were the major contributors, followed by lead exit related failures, irrespective of application or manufacturing period. Dielectric mode failures were the most prominent, followed by mechanical and electrical type failures, for substation transformers, whereas GSU transformers had higher contributions of thermal and dielectric mode failures.