IEEE Transactions on Sustainable Energy · 2017 · 120 citations · 3 references
EngineeringElectrical EngineeringSystems EngineeringDynamical SystemsEnergy SystemsSystem DynamicsDistributed Energy ResourcesPower Grid AnalysisPower Plant Control SystemsPower System StabilityVoltage RegulationWind Energy SystemsNetwork OscillationsPower Oscillation DampingRoot Cause DeterminationSmall-signal Stability AnalysisSystem Stability AnalysisUndamped OscillationsWeak Grid StabilityWind Power Systems
An existing wind power plant at ERCOT experienced poorly damped and undamped voltage oscillations under weak grid conditions. The oscillations became worse during high power outputs. This letter aims to find the root cause of such oscillations. Our research provides a linearized system model by combining the vector control of wind power plants and the weak grid interconnection. Using this model, this letter succeeds in explaining that the weak grid condition introduces a zero in right half plane for the open-loop system, which can lead to poorly damped or undamped oscillations.
3
Dynamic modeling of GE 1.5 and 3.6 MW wind turbine-generators for stability simulations
N.W. Miller, J.J. Sanchez-Gasca, W.W. Price et al. · 2003 IEEE Power Engineering Society General Meeting (IEEE Cat. No.03CH37491) · 2004 · 455 citations
Engineering, Systems Engineering, Model-based Systems Engineering +16