2016 · 17 citations · 11 references
EngineeringElectrical EngineeringCircuit TheoryPower ElectronicsSecondaryCurrent-voltage CharacteristicsElectrical System DiagnosticsFault DetectionPower QualityPower SystemsProtection SystemsCurrent Signature AnalysisCurrent-based Fault DiagnosisMathematical MorphologyReal-time ProcessingRelay ProtectionSecondary Current DistributionTransformer ProtectionWavelet Transform Analysis
Current transformers (CTs) may saturate during internal fault, external fault, over excitation, exciting inrush current and other phenomena, which would cause protection relay malfunction or even tripping. As a result, it is vital to mitigate the adverse effects of CT saturation. By analyzing the secondary current waveform, which has abrupt changes where saturation begins and ends, the paper proposes a detection method that combines morphological gradient wavelet (MGW) and morphological opening-closing and top-hat operators to accurately detect the onsets and ends of saturations in real time. The paper also presents a compensation method to reconstruct healthy secondary current waveforms. The proposed saturation detection and compensation methods are implemented and tested on a sample power system model built in PSCAD/EMTDC, and simulation results show that the proposed methods can successfully detect the saturation sections and compensate the distorted secondary current under a variety of operation conditions.
11