Concepedia

Publication | Closed Access

Morphological Lifting Scheme for Current Transformer Saturation Detection and Compensation

80

Citations

19

References

2008

Year

Abstract

Current transformer (CT) saturation can cause protective relay mal-operation or even prevent tripping. The wave shape of the secondary current is severely distorted as the CT is forced into deep saturation when the residual flux in the core adds to the flux change caused by faults. In this paper, a morphological lifting scheme is proposed to extract features contained in the waveform of the signal. The detection of the CT saturation is accurately achieved and the points of the inflection, where the saturation begins and ends, are found with the scheme used. This paper also presents a compensation algorithm, based upon the detection results, to reconstruct healthy secondary currents. The proposed morphological lifting scheme and compensation algorithm are demonstrated on a sample power system. The simulation results clearly indicate that they can successfully detect and compensate the distorted secondary current of a saturated CT with residual flux.