Publication | Closed Access
Detectability of Degraded Joint Discontinuities in HV Power Lines Through TDR-Like Remote Monitoring
29
Citations
21
References
2016
Year
EngineeringMeasurementRemote DiagnosticsHv Power LinesEducationCondition MonitoringReliability EngineeringDegraded Joint DiscontinuitiesPower Transmission LinesSystems EngineeringElectric Power TransmissionInstrumentationElectrical EngineeringTdr-like Remote MonitoringDegraded CompressionStructural Health MonitoringPower System ProtectionElectrical TransmissionCivil EngineeringRemote MonitoringTransmission Line
The aim of this paper is to clarify some important aspects associated with the possibility to detect degraded compression and bolted joints in power transmission lines using a time-domain reflectometry (TDR)-based remote monitoring. The optimization of a TDR-based remote monitoring method is discussed, studying the effects of the source impedance, source-to-line connection, line characteristic impedance, and scope settings, providing useful guidelines for a future method and instrumentation refinement. The experimental results are presented consisting in the inclusion of lumped resistors of several values along a 130-kV power transmission line. The minimum detectable resistance is discussed based on the present available hardware. The TDR-based method is shown to be able to also identify the main features of the line layout such as phase transpositions and different heights of adjacent towers. This paper represents a preliminary base to keep developing the proposed method, with the aim to overcome the actual limitations (costs, reliability, etc.) in power line monitoring.
| Year | Citations | |
|---|---|---|
Page 1