Water Science & Technology · 2001 · 22 citations · 2 references
EngineeringEnvironmental EngineeringWastewater ReuseWastewater TreatmentWater TreatmentConstructed WetlandsNitrogen RemovalNutrient RemovalSecondary TreatmentSludge TreatmentTertiary TreatmentConstructed Wetland TreatmentHydraulic PerformanceMunicipal Wastewater TreatmentNutrient Removal In WetlandsOrganic Loading RateWastewater Treatment Nutrient RemovalWastewater Treatment ProcessesWater Treatment Systems
The performance of 4 constructed wetlands designed by IRIDRA Srl and operating in Tuscany (central Italy) has been monitored during the last three years. The 4 treatment systems have different sizes and characteristics: one single stage secondary treatment (150 p.e.); two secondary treatment plants with effluent reuse: one small (60 p.e) and the other big (350 p.e.); a tertiary treatment of effluents from an activated sludge plant with high hydraulic load fluctuation (5-500 p.e.). Due to geographical and economic constraints the four systems have high hydraulic and organic loading rates, neverthless the systems show very good removal performance of COD (62-95%), especially the ones with higher inflow COD concentrations (87-95%). Interesting results concerning also removal percentage of MBAS (42-88%) and ammonium (42-85%) were obtained, even though NH4+ concentration in the outflows of some of the plants, doesn't always comply with Italian quality standards.
2