Journal of International Crisis and Risk Communication Research · 1998 · 18 citations · 0 references
Open access
EngineeringBuilding ScienceAir ConditioningHeat TransferThermal ComfortBuilding Cooling SystemsBuilding Energy SystemsBuilding Thermal PerformanceRoof DesignThermal PerformanceThermal Performance AssessmentCommercial Building EfficiencyCommon Base ConfigurationCooling Load AnalysisPeak Cooling Load ReductionPower ConditioningReflective Roofing
This paper reports on the first results from tests on a reflective roofing system on a commercial building in Florida. The building is a elementary school with a sloped, modified bitumen roof. Air-conditioning power was measured in a base configuration prior to the roofing system being changed to a white color. Roof, decking, and plenum air temperatures were strongly affected by the change to a white roof system. The school, which was monitored for a full year in both the pre- and post-condition, saw the measured annual chiller electric power reduced by 10%, or 13,000 kWh/yr. Cooling-load reductions during the utility summer peak were substantially greater, more than 30% during the afternoon hours.