2007 · 22 citations · 8 references
EngineeringElectrical EngineeringCircuit TheoryElectric MachinesPower ElectronicsPower SystemsProtection SystemsOvervoltage TransientsPower System Fault TransientsSwitching TransientsTransformer ProtectionTransient Overvoltages
This paper presents the explosive problem of riser pole arresters during the operations of disconnector switches in the feeder having a station service transformer. In order to determine the cause and the practical solutions, field tests and computer simulations with ATP/EMTP program were conducted. The field tests revealed that in the case of switching without arrester installation, chaotic transient and 3 rd sub-harmonic overvoltages appeared in the opened phase during switching. In the case of switching with arrester installation, the restricted spike overvoltages were found. The arrester on the last closed phase exploded because it suffered ferroresonant overvoltages for a long time. The simulation results agree with the results of field test. They show that the switching angle has significant effects on ferroresonant initiation, and associated overvoltages. To avoid and mitigate ferroresonant overvoltages, alternation of switching procedures and application of a resistive load were considered. The results of counter-measures were verified by using both simulations and field tests.