Analysis of nonlinear phenomena in MOV connected transformer

Kassim A. Al-Anbarri, R. Ramanujam, T. Keerthiga, K. S. Kuppusamy

IEE Proceedings - Generation Transmission and Distribution · 2001 · 27 citations · 12 references

Concepts

Abstract

This paper investigates the effect of a metal oxide arrester on the ferroresonance behaviour of a transformer connected in parallel. It is known that the arresters may in some cases cause ferroresonance ‘dropout’. This aspect is examined in detail here by proper modelling of the nonlinear characteristics such as arrester characteristics and transformer saturation. Time-domain simulation has been carried out using a fourth-order Runge–Kutta method and the results were corroborated using EMTP. The results reveal that the presence of the arrester has a mitigating effect on ferroresonant overvoltages. Extensive simulations have been carried out to analyse the sensitivity with respect to arrester parameters, transformer saturation characteristics and the amplitude of the voltage source occurring in the Thevenin equivalent of the circuit. The presence of the arrester has a significant effect on the onset of chaos, the range of parameter values for which chaos persists and the magnitude of ferroresonant over voltages.

References

12