Composition shifts of zeotropic HFC refrigerants in service

Stuart J. Corr, Fionnuala Murphy, Simon Wilkinson

OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) · 1994 · 14 citations · 0 references

Concepts

Abstract

Two contributing mechanisms to the composition shifts observed when using zeotropic hydrofluorocarbon (HFC) refrigerants in refrigerating and air-conditioning applications have been investigated using both computer modeling and experimental techniques. The major distinguishing features of the model are the inclusion of refrigerant-lubricant interactions and the composition shifts associated with vapor-liquid volume fraction effects in zeotropic refrigerants. this paper describes the computer model and illustrates the behavior of some HFC refrigerants as a number of refrigeration system parameters are varied.