Detection of Subsynchronous Torsional Oscillation Frequencies Using Phasor Measurement

Tuomas Rauhala, A.M. Gole, Pertti Järventausta

IEEE Transactions on Power Delivery · 2015 · 43 citations · 9 references

Concepts

Abstract

This paper presents a noninvasive and easy-to-implement technique using phasor measurement units for accurate estimation of subsynchronous torsional frequencies. This information is relevant for the optimal design of high-voltage direct-current (HVDC) subsynchronous damping controllers that enhance the effect of HVDC on subsynchronous damping. The method is rigorously justified using mathematical proofs as well as thorough electromagnetic-transients simulations. The method was implemented in the Finnish transmission network and proved to be effective.

References