Due to government policies incandescent lamps are more and more replaced by modern energy saving lamps worldwide. Compared to incandescent lamps luminaries using new technologies (e.g. compact fluorescent and solid state lamps) have a decreased damping effect and significant harmonic emissions, mostly at low order frequencies. Current harmonic limits for these lamps are specified in IEC 61000-3-2. For lamps with rated power below 25W these limits were defined taking several assumptions into account. One assumption is a significant cancellation effect of harmonics between energy saving lamps and other electronic equipment, like computers or TV sets. The main intention of the paper is to verify the cancellation effect for currently available lamps and typical electronic household equipment. After a short introduction and description of the test setup the harmonic emissions of more than 100 lamps (CFL and SSL) and more than 50 electronic appliances, mainly with rated power below 75W, are presented. The cancellation effect of the 5th harmonics for different scenarios is discussed and finally some field measurements are analyzed. ABBREVIATIONS
3
P.N. Korovesis, Georgios A. Vokas, Ioannis F. Gonos et al. · IEEE Transactions on Power Delivery · 2004 · 59 citations · Full text