Harmonic emission before and after changing to LED and CFL — Part II: Field measurements for a hotel

Sarah Rönnberg, Mats Wahlberg, Math Bollen

2010 · 38 citations · 0 references

Concepts

Abstract

This paper shows the results of measurements performed with a medium-sized hotel in the North of Sweden. The harmonic emission and other parameters were measured before, during and after a replacement of all incandescent lamps with energy saving lamps, both compact fluorescent lamps (CFL's) and light emitting diodes (LED's). it was not possible to see any major difference in harmonic spectrum before and after the replacement. The reduction in power factor that was observed was completely due to the reduction in active power.