IEEE Transactions on Power Apparatus and Systems · 1963 · 10 citations · 3 references
Natural SciencesElectrical EngineeringPhysicsCritical Infrastructure ProtectionElectromagneticsElectromagnetismInsulation MaterialsInsulation SystemsLightning CurrentLightning ProtectionProtection SystemsThunderstorm ElectricityCable InsulationCapacitorsElectrical InsulationLightning Current In Power SystemsLightning Induced VoltagesLightning Surge ProtectionSurgeSurge Protective Devices
Insulating sheath coatings and sheath-joint insulators have been punctured in service, apparently by transient voltages. It has been shown that the discontinuities caused by sheath cross-bonding result in 15% of an applied surge on a conductor, appearing on the sheath at a joint and 30% across the sheath insulator. Bonding transformers result in higher transients. Protective devices appear to be required at each joint. These may be lightning arresters or surge capacitors.
3
Transient voltages on bonded cable sheaths
Herman Halperin, J. E. Clem, K.W. Miiler · Electrical Engineering · 1935 · 11 citations