IEEE Transactions on Power Delivery · 2010 · 152 citations · 23 references
EngineeringElectrical EngineeringEnergy SystemsPower ElectronicsRenewable Energy SystemsConverter TopologiesDc-dc ConvertersPower Electronics For Renewable EnergyPower SystemsThree-phase CircuitsVoltage RegulationConvertersDynamic Voltage RestorationDynamic Voltage RestorerEnergy Storage ElementsPower ConvertersSingle-phase ConvertersThree-phase ConvertersVoltage Control
In this paper, two new topologies are proposed for three-phase dynamic voltage restorers (DVRs). These topologies are based on direct converters. The proposed topologies do not require dc-link energy storage elements. As a result, they have less volume, weight, and cost. They can also compensate long-time voltage sags and swells. The proposed DVRs can compensate several types of disturbances, such as voltage sags, swells, unbalances, harmonics, and flickers. Moreover, due to the fact that the compensation voltage for each phase is taken from all three phases, the proposed topologies can compensate one-phase outages. In the proposed topologies, three independent three-phase to single-phase direct converters are used. Each converter operates independently and, as a result, the proposed DVRs properly compensate unbalanced voltage sags and swells. The used converters can be constructed by four or six power switches. Depending on the structure of the used converters, the compensation ranges will be different. A new control method is also proposed for using direct ac/ac converters. The experimental and simulation results verify the capabilities of the proposed topologies in compensation of voltage distortions.
23