The transient response of an evaporator fed through an electronic expansion valve

A. Outtagarts, Philippe Haberschill, M Lallemand

International Journal of Energy Research · 1997 · 75 citations · 0 references

Concepts

TL;DR

An expansion valve in a refrigeration system controls evaporator mass flow to achieve optimal operation without hunting. The study develops two stepper‑motor‑controlled valve algorithms—proportional/derivative and qualitative optimal regulation—to manage valve opening and closing. Tests were performed on a <6 kW refrigeration unit with fixed condensation, variable evaporating temperatures (−20 °C to +10 °C) and compressor speeds (1000–3000 rpm), and control parameters were tuned based on the transfer functions of the valve and evaporator. The system remains stable at steady state with superheat at the set value, and during transients—including 300 rpm and 1000 rpm step changes and cold starts—the algorithms effectively regulate refrigerant flow into the evaporator. © 1997 John Wiley & Sons, Ltd.

Abstract

The primary task of an expansion valve in a refrigerating machine is to control the mass flowrate into the evaporator to obtain optimal operation without 'hunting' under given conditions. A stepper-motor-controlled expansion valve and an evaporator have been studied. The tests were carried out on a fixed refrigerating machine of cooling capacity less than 6 kW, with constant condensation conditions and variable evaporating temperature (−20 to +10°C) and compressor speed (1000 to 3000 r.p.m). Two control algorithms (proportional/derivative and qualitative optimal regulation) have been developed for opening and closing the valve with the stepper motor. The control parameters depend on both the expansion valve and the evaporator transfer functions. In steady-state conditions, the system is stable with a superheat equal to the set value. Under transient conditions, with step excitations of 300 and 1000 r.p.m as well as for cold-start of the machine, the control algorithms are adequate for regulating the refrigerant flowrate into the evaporator. © 1997 John Wiley & Sons, Ltd.