IEEE Transactions on Power Delivery · 1990 · 15 citations · 6 references
EngineeringElectrical EngineeringNuclear EngineeringCritical Infrastructure ProtectionNuclear Safety AnalysisReactor PhysicsElectrical System DiagnosticsReactor Protection SystemsArc Fault DetectionCable System DesignEscalationHigh-voltage BreakdownOvervoltage TransientsTransmission Line TransientsVoltage Interruption
A 150 MVA reactor current interruption test using a GIS (gas-insulated switchgear) on an actual 275 kV cable system and a laboratory high-frequency current interruption test using a 300 kV SF/sub 6/ gas circuit breaker were conducted. The results of these tests and their analyses, made simultaneously, permitted (1) the calculation of reignition surges and the detection of high-frequency arc extinctions caused when the reactor current was interrupted by a GIS on a cable system and (2) an evaluation of voltage escalation caused at high-frequency arc extinctions.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>