IEEE Transactions on Power Delivery · 2001 · 63 citations · 8 references
EngineeringElectrical EngineeringPhysicsCircuit TheoryHvac SystemsPower ElectronicsAc-dc ConvertersDc-dc ConvertersElectric CircuitsArc DischargesCircuit Breaker ProtectionCoupled Lc CircuitsLc OscillatorsSelf-excited OscillationsVoltage Gradient
The Kii-Channel HVDC Link under construction in Japan is equipped with metallic return transfer breakers (MRTBs) in one converter station. A new MRTB for an interrupting current of 3500 A DC was developed. To interrupt a DC current, a method that produces a current zero point by superimposing a self-excited oscillatory current on a DC arc current was employed. For this purpose, a LC circuit was coupled in parallel to a SF/sub 6/ gas circuit breaker. Developing a SF/sub 6/ gas circuit breaker that has a large arc voltage drop gradient against currents permitted a large oscillatory current to be generated. A modified Mayr-type dynamic arc equation was newly presented. The DC interruption limits calculated using this equation agreed with the measured values.
8
Development of a 500kV Airblast HVDC Circuit Breaker
Björn Bachmann, G. Mauthe, E. Ruoss et al. · IEEE Transactions on Power Apparatus and Systems · 1985 · 97 citations
The Development of a HVDC SF6 Breaker
A. Lee, Paul G. Slade, Kyoungro Yoon et al. · IEEE Transactions on Power Apparatus and Systems · 1985 · 27 citations