IEEE Power Engineering Society General Meeting, 2005 · 2005 · 238 citations · 1 references
AgricultureElectrical EngineeringRenewable Energy IntegrationRenewable Energy SystemsWind EngineeringFrequency RegulationPower Grid AnalysisPower SystemsRenewable EnergyVoltage RegulationWind Energy SystemsFault Ride-throughFault Ride-through CapabilityFault Ride-through ControlFault Ride-through ProtectionPower System OperationWindWind Power IntegrationWind Power Systems
This paper discusses issues of German grid codes relating to wind turbines. With the high utilization of wind power a simultaneous loss of several thousand MW wind generation became a realistic scenario in the German power system. Therefore, the main requirements concern the fault ride through capability of wind turbines. Accordingly, disconnection of wind turbines and wind farms above 15 % nominal voltage at the grid connection nodes is not allowed. Besides, following network faults wind turbines have to supply a definite reactive current depending on the instantaneous voltage. Furthermore, they must return quickly to normal operation. The frequency range wind turbines have to tolerate is about 47.5-51.5 Hz. According to the wishes of German transmission grid operators, large wind farms have to be treated in the future like conventional power plants.
1
Grid Code, high and extra high voltage
E.on Netz · Medical Entomology and Zoology · 2006 · 577 citations