Coordination of a distribution level continuously controlled compensation device with existing substation equipment for long term VAr management

John Paserba, D.J. Leonard, N.W. Miller, Sebastian Naumann, M. G. Lauby, F.P. Sener

IEEE Transactions on Power Delivery · 1994 · 72 citations · 3 references

Concepts

Abstract

The implementation of a continuously-controlled reactive compensation device, such as an SVC or a "static condenser" (STATCON), in a distribution-level substation provides opportunities to improve power quality and reliability due to the speed of response of such a device. Further benefits can be gained by coordinating the reactive compensation device and its related controls with other substation voltage control equipment, such as load tap changing (LTC) transformers and mechanically-switched capacitors. The results presented in this paper illustrate the impact that a /spl plusmn/12 MVAr STATCON can have on a 150 MW, 12.5 kV load bus, in the Commonwealth Edison power system. Three control concepts for various levels of integration of the substation STATCON, LTCs, and mechanically-switched capacitors are presented. With broader application of SVCs and STATCONs at distribution substations, various other control strategies may also evolve.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>