Investigation on abnormal phenomena of contacts using disconnecting switch and detachable bus in 300 kV GIS

Yoku Mukaiyama, I. Takagi, Kunikazu Izumi, Terukazu Sekiguchi, Atsushi Kobayashi, Toshio Sumikawa

IEEE Transactions on Power Delivery · 1990 · 32 citations · 3 references

Concepts

Abstract

Using the disconnecting switch and the detachable bus of a gas-insulated switchgear (GIS), rated voltage 300 kV and rated current 2000 A, current and voltage-current tests were conducted in simulation of abnormal contact likely to occur in actual operations, yielding the following results: under the abnormal condition of the arcing contact of the disconnecting switch, continuous arcing occurs with a current above a certain level, resulting in a ground fault. Under the abnormal condition of the main contacts of the disconnecting switch, continuous arcing occurs, resulting in a ground fault if products decomposed by arcing are deposited on the contacts. In conductors of the detachable bus, arcing occurs with current above a certain level if there is a gap between the current-carrying surfaces even when bolts are used. The progress thereafter can be roughly divided into two categories. With narrow gaps between the current-carrying surfaces, the current-carrying surfaces are welded together with the molten metal produced by arcing. With wide gaps between the current-carrying surfaces, continuous arcing occurs. Rapid overheating or arcing at contacts is likely to occur not only when the current is raised by also when sunlight shifts.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>