IEEE Transactions on Power Systems · 2012 · 112 citations · 28 references
EngineeringElectrical EngineeringPower ElectronicsRegulatory ComplianceRenewable Energy SystemsAdaptive ControlControl TheoryPower ControlPower Plant Control SystemsPower System StabilityPower SystemsCompliance Requirements AnalysisFinite Impulse Response FiltersInterference RejectionPower System StabilizationRegulatory Compliance AnalysisResponse TimeStability ControlSystem Stability Analysis
For the first time, IEEE Std. C37.118.1-2011 now provides metrics for PMU dynamic performance in terms of classes P and M filter designs. This paper attempts to determine whether fulfilling these requirements makes the PMU inherently well suited for stability control applications such as wide-area power system stabilizers (PSSs). In this aim, we considered two different frequency-adaptive approaches for class-P and -M compliance to ensure operation over a wide frequency range. The first is based on a finite-impulse response (FIR) with no overshoot in either the phase or the amplitude step responses, while the second is Kalman filter-based (EKF), which allows for a more refined out-of-band interference rejection at the cost of a phase step response with overshoot. These two approaches are benchmarked against Hydro-Québec`s existing PSS requirements and the conclusion is that the total vector error-based response time is not indicative of the phase lag within the frequency band of interest, nor of the 3-dB bandwidth under sinusoidal amplitude/frequency modulation phenomena, which are key criteria when specifying PSS PMUs. Using simulated and field-recorded network fault responses, we also show that a class-M PMU is unsatisfactory for wide-area stabilizing control, unless its performance is improved during the fault period, which is not covered by Std. C37.118.1-2011.
28