IEEE Transactions on Power Delivery · 2010 · 166 citations · 19 references
EngineeringElectrical EngineeringInstrumentationPower ElectronicsTime Series AnalysisDigital Signal ProcessingFrequency-domain AnalysisState EstimationSteady-state AnalysisBalanced Three-phase SystemsDiscrete Fourier TransformFourier TransformPhase-locked LoopsPhasor Measurement UnitsSteady-state OperationUnbalanced Three-phase Systems
This paper introduces the application of an enhanced phase-locked loop (EPLL) system to the estimation of synchrophasors in a phasor measurement unit (PMU). The major concern is accurate estimation within off-nominal frequency operation of the system. The well-known technique based on discrete Fourier transform (DFT) can provide accurate estimation of the phasors in a three-phase balanced system. However, the negative-sequence component causes errors to the DFT estimates. The DFT cannot accomplish this task in a single-phase system. The EPLL is shown to be a solution for those shortcomings of the DFT technique, both in single-phase and in unbalanced three-phase systems, at the expense of some more complicated structure. Extensive steady-state and dynamic tests are performed and the results are presented and discussed.
19
Ramachendra P. Batni · Journal of the Franklin Institute · 1972 · 1.1K citations
The Wide World of Wide-area Measurement
A.G. Phadke, Hector A. R. Volskis, Rui Menezes de Moraes et al. · IEEE Power and Energy Magazine · 2008 · 294 citations
Engineering, Electrical Engineering, Systems Engineering +15