Feasibility of On-Line Monitoring of the BTU Content of Natural Gas with a Near-Infrared Fiber Optic System
24
Citations
10
References
1993
Year
EngineeringMeasurementGas SensorEducationFiber OpticsTotal Energy ValuesEnergy ContentBtu ContentOn-line MonitoringOptical DiagnosticsCalibrationThermal Infrared Remote SensingInstrumentationInfrared SpectroscopyFiber Optic SensingNear-infrared SpectroscopyOptical SensorsInfrared SensorSpectroscopy
Optical-fiber measurements coupled with near-infrared spectra in the range of 5500 to 10,000 cm −1 are used to determine the optimum spectral region for remotely monitoring the energy content of natural gas at above ambient pressures. The system was configured with a Fourier transform near-infrared spectrometer and a fused-silica fiber bundle. The total energy values at a pressure of 100 psi were determined by the partial least-squares (PLS) calibration algorithm. The precision and accuracy for predicting the BTU content of an industry standard gas sample were less than 0.4% in the lower-frequency region of 5700 to 6400 cm −1 .