Electrical EngineeringDielectricsEngineeringPressboard InsulationTemperature DependenceElectric FieldAc StrengthDielectric StrengthThermal InsulationElectrical Insulation
This work reports on measurements investigating the dielectric strength of insulating oil and Transformerboard, from very low (-20/spl deg/C) to increased temperature (+60/spl deg/C). Different insulation structure models-board puncture and creepage-were stressed with 1 hour DC step-by-step voltage increase of reversed polarity each step, until breakdown. The impact of adhesives and their orientation relative to the electric field was investigated. As a reference, the AC strength and the moisture content of the oil was measured. With the results from this study, important knowledge of the DC behavior of oil/cellulose insulation is gained. The findings constitute a profound basis for improved HVDC power transformer insulation technology.
1
Moisture equilibrium in transformer paper-oil systems
Yanqing Du, Markus Zahn, Bernard C. Lesieutre et al. · IEEE Electrical Insulation Magazine · 1999 · 369 citations · Full text