IEEE Transactions on Industrial Electronics · 2009 · 114 citations · 21 references
EngineeringElectrical EngineeringCircuit TheoryFinite Element AnalysisPower ElectronicsNonlinear Finite Element AnalysisPower QualityCore Loss ModelingFinite Element Transient AnalysisHarmonic EffectsHysteresisHysteresis PropertiesLoad-dependent LossesNo-load LossesNo-load Operation
The losses in European Union distribution transformers are estimated at about 33 TW ·h/year, whereas reactive power and harmonic losses add a further 5 TW ·h/year. The reduction of distribution transformer no-load loss is particularly important as the ratio of no-load to load losses is nearly three. In this paper, the no-load operation of wound-core transformers under sinusoidal and distorted supply-voltage conditions is investigated. For that purpose, a 2-D nonlinear transient finite-element analysis taking into account hysteresis has been developed. The hysteresis model is based on a modified Jiles-Atherton representation, and the proposed analysis is compared to experimental data.
21
Patricio Flores, J. Dixon, M. Ortuzar et al. · IEEE Transactions on Industrial Electronics · 2009 · 157 citations · Full text
Themistoklis D. Kefalas, Pavlos S. Georgilakis, Antonios G. Kladas et al. · IEEE Transactions on Magnetics · 2008 · 59 citations · Full text
Engineering, Materials Engineering, Computational Electromagnetics +13