IEEE Transactions on Power Electronics · 2011 · 86 citations · 18 references
EngineeringElectrical EngineeringCircuit TheoryEnergy SystemsPower ElectronicsConverter TopologiesHigh-frequency Power ConversionPower System StabilityPower SystemsThree-phase CircuitsVoltage RegulationDynamic Voltage RestorationDynamic Voltage RestorerInrush CurrentInrush Current MitigationIsolated Converter TopologiesPid Control DesignSmall-signal Equivalent Circuit ModelsThree-phase Circuit Modeling
Conventional dynamic voltage restorers (DVRs) are connected to the power grid through power-frequency transformers. These bulky and costly transformers cause voltage drop and power losses. In this paper, a high-frequency-link dynamic voltage restorer (HFL-DVR) is proposed based on transformer-isolated topologies. This topology facilitates independent operation conditions for each phase in a three-phase system. It enjoys relatively low cost, low losses, and small size. Also, it is free from transformer inrush currents. Small-signal ac equivalent circuit for the power stage including HFL-DVR is derived based on an averaged modeling approach. Transfer functions are obtained to study the effect of inputs such as dc-link voltage, grid voltage, and the load current on the output of HFL-DVR. In order to obtain acceptable properties such as transient overshoot, setting time, and steady-state error, a PID controller is added to the system. This shows that the effect of disturbances on the output of HFL-DVR can be reduced. The experimental results are obtained from a 220V/50Hz HFL-DVR setup. The simulation and experimental results have been compared to verify theoretical aspect of the proposed DVR for both symmetrical and asymmetrical voltage sag conditions.
18