IEEE Transactions on Industry Applications · 2011 · 14 citations · 7 references
EngineeringElectrical EngineeringEnergy SystemsFire Protection EngineeringHeat TransferElectrical InstallationElectrical SafetyFire PreventionFire SafetyFire TestingHeat Stress AssessmentCurrent MetersElectrical Equipment Fire ProtectionElectromagnetic Current MetersFlash Fire ProtectionMeasured Energy PerformanceTest Program Design
A test program was completed to measure arc-flash incident energy from actual 480-V utility equipment to determine the most appropriate flame resistant clothing for utility workers. The equipment tested included self-contained and current transformer-rated meters, pad-mounted transformer secondary cubicles, power panels, and network protectors. Testing was performed to determine the sustainability of low-voltage arcs in actual utility equipment, to find the most appropriate calculation method to predict the measured incident energy, and to identify any key variables that would effect both duration and heat from this type of equipment.