EngineeringElectrical EngineeringElectromagneticsHazard IdentificationSafety EngineeringElectrical Hazard AssessmentElectrical Hazard IdentificationElectrical SafetyElectrical System TestingHazard AnalysisArc DischargesArc Flash Hazard AssessmentArc Plasma PhysicsCurrent LimitingElectrode GeometryElectrode InterfacesFault Current LimitingFuses
The arc flash hazard calculation method proposed in IEEE 1584 is based on tests with the arcing electrodes in a vertical plane and the calorimeters arranged at 90/spl deg/ to this plane. In this paper the results of tests using the IEEE test set-up with both vertical and horizontal electrodes are given. High-speed videography and incident energy measurements show that the arc flash hazard is much worse with the horizontal orientation. However current-limiting fuses are effective in limiting the incident energy, even in worst-case arcing conditions, provided that the bolted-fault current is high enough to cause them to operate in their current-limiting mode. The incident energy values are shown to depend on the size of the trigger fuse wire used. The effect of phase imbalance is also considered.